Detail Velcon VF Series Vertical Filter Vessel Model VF814150 Velcon VF Series Vertical Filter Vessel Model VF2044150 Velcon VF Series Vertical Filter Vessel CUTAWAY Velcon FO Series Cartridge Velcon AC Series Cartridge Cutaway Velcon FG Series Cartridge Cutaway
STANDARD DESIGN FEATURES
150 psi welded steel ASME Code construction.
Choice of micron rating from 0.5 to 75 microns.
Choice of pleated or depth type media.
Epoxy coated interior, primed exterior.
Buna-N O-ring cover seals.
RECOMMENDED OPTIONAL ACCESSORIES
Automatic Air Eliminator
Pressure Relief Valve
Differential Pressure Gauge
Drain Valve( s)
Sampling Probes
ASME Code Stamp
TYPICAL APPLICATIONS
Jet Fuel
Gasoline
Diesel Fuels
Jump through to your choice of Filter Vessel and Cartridge Ranges
VF Series Filter Vessels
FO Series - Pleated Media Filter Cartridges
AC Series - Aquacon Water Absorbing Cartridges
FG Series - Fibreglass Cartridges
Consult our cartridge data sheets to select the micron rating and type of cartridge that is right for your application ? PLF Series ( pleated surface type filtration) , FG Series ( fiberglass depth type filtration) , or Aquacon Series ( dehydration and filtration) .
Filter vessels VF814 through VF844, such as the VF814150 shown at right, have through-bolt covers, NPT connections, and include fittings for drain, pressure gauge and air vent.
VF1614 and larger vessels, such as the VF2044150 shown at top right, are provided with swing bolt closure, RF flange connections and fittings for pressure gauge, air eliminator, pressure relief valve and drain valve.
Note: In applications where increased dirt contamination is present, it may be desirable to oversize filtration equipment. Contact PETRO for oversizing recommendations. For API/ EI applications, please consult PETRO
PRODUCT RANGE
VF Series Filter Vessel
Vessel Model Number
Maximum Flow
USGPM
FO Series Cartridges
Weight with skid, lbs.
Volume U.S. Gallons
Jet Fuel
Gasoline
Diesel
Length
Qty
VF814
67
68
65
14
1
225
5
VF829
13 3
136
130
29
1
265
8
VF844
200
204
195
44
1
305
11
VF1614
267
2 72
260
14
4
500
22
VF1629
533
544
520
29
4
560
35
VF1644
800
816
780
44
4
620
48
VF2029
800
816
780
29
6
1000
67
VF2044
1200
122 4
1170
44
6
1100
88
VF2829
1600
1632
1560
29
12
1500
125
VF2844
2 400
2448
2340
44
12
1600
165
VF3644
3600
3672
3510
44
18
2250
28 8
VF4244
5400
5508
5265
44
27
3800
400
Flow rates are for FO-614PLF series pleated paper cartridges. For higher viscosity fluids, consult your PETRO Representative.
VF Series Filters are designed to accommodate our standard 6 in. O.D., 3.5 in. I.D., 14.5 in. long cartridges that are stacked one, two, or three high. Many cartridges are available in longer lengths that eliminate stacking. For example, a 44 inch long FO-644PLF1M could be used in place of three 14.5 inch long cartridges. This makes for easier and less expensive changeouts.
A number of threaded base filter cartridges ( e.g. FO-644PLF5TB) are available, which allow for easier cartridge changeout and removal of particulate matter from the deckplates. See data sheet # 1549. The threaded base cartridges mount on the 6000T Adapters.
Dimensions shown are for estimating purposes only. For exact dimensions, obtain certified drawing.
VF16 and VF20 Series vessels have flat covers. VF16 Series vessels do not have hydraulic lift jacks.
Available Aquacon Cartridges are AC-6xx05 and AD-6xx25 where xx represents cartridge lengths of 14, 29, and 44 inches.
FO SERIES - PLEATED MEDIA FILTER CARTRIDGES
High Efficiency, Long Life Cartridges for Industrial Fluids
Large Surface Area ? Allows high flow rate with low initial pressure drop and maximum
contaminant holding capacity.
Resin Impregnated Media ? Maintains strength, resists effects of water and heat.
75 psi Collapse Strength ? Heavy gauge carbon steel center tubes give safety margin
against pressure surges.
Coated Steel Components ? Resist corrosion from most industrial fluids.
Corrugated Media ? Prevents pleat pinch-off, assuring all filtration media is utilized.
Buna-N Gaskets ? The best general gasket material available assures positive seal in most fluids.
Thermoset Bonding Material ? Durable endcap-to-media bond prevents internal bypassing
Threaded base filter cartridges ? Available for easier installation.
APPLICATIONS
Velcon Pleated Media Cartridges are suitable for a broad range of polar and non-polar fluids. Recommended for applications where the contaminant is granular ( non-colloidal) , allowing maximum utilization of the high surface area.
Suitable for:
All Hydrocarbon Fuels
Cutting Oils
Glycols
Degreasing Fluids
Water Emulsion Coolants
Naphtha
Lube Oils
Ethyl Alcohol
Insulating Oils
Toluol
Synthetic Oils
Hydraulic Oils
DieselFuel
Biodiesel Fuel
SPECIFICATIONS
Recommended changeout differential pressure - 25 psid
75 psi Collapse strength
Micron ratings from 1/ 2 to 75
98% + Nominal filtration efficiency
5 - 9 Operating pH range
250 F Maximum operating temperature
Multi-pass ( Beta Ratio) data available on request
For information about Flow Ratings with various viscosity fluids, refer to Form # 1532
CARTRIDGE INFORMATION
The following table lists a few of the broad range of available Velcon cartridges and some of their common interchanges. Your local Velcon Representative can provide more complete information.
Dimensions Model Nominal Micron Rating Protective Outer Wrap
4? x 12 ? x 1 ? ID FO-412PL2 2 No
FO-412PL5 5 No
4? x 18? x 1 ? ID FO-418PL5 5 No
FO-418PL15 15 No
For VF-61 Housing FO-512PL1/ 2 0.5 No
FO-512PL05 5 No
FO-512PL25 25 No
6? x 14 ? x 3 ? ID FO-614PLF1/ 2 0.5 No
FO-614PLF1 1 No
FO-614PLF2 2 No
FO-614PLF5 5 No
FO-614PLF5M 5 Yes
FO-614PLF10 10 No
FO-614PLF15 15 No
FO-614PLF15M 15 Yes
FO-614PLF25 25 No
FO-614PLF25M 25 Yes
FO-614PLF75 75 No
6? x 29? x 3 ? ID FO-629PLF1/ 4 0.25 Yes
FO-629PLF1/ 2 0.5 Yes
FO-629PLF1 1 Yes
FO-629PLF2 2 Yes
FO-629PLF5 5 Yes
FO-629PLF10 10 Yes
FO-629PLF20 20 Yes
FO-629PLF25 25 Yes
6? x 29? Threaded Base FO-629PLF1/ 2TB 0.5 Yes
FO-629PLF1TB 1 Yes
FO-629PLF2TB 2 Yes
FO-629PLF5TB 5 Yes
FO-629PLF25TB 25 Yes
6? x 44? x 3 ? ID FO-644PLF1/ 2 0.5 No
FO-644PLF1M 1 Yes
FO-644PLF2M 2 Yes
FO-644PLF5M 5 Yes
FO-644PLF10M 10 Yes
FO-644PLF15M 15 Yes
FO-644PLF25M 25 Yes
6? x 44? Threaded Base FO-644PLF1/ 4TB 0.25 Yes
FO-644PLF1/ 2TB 0.5 Yes
FO-644PLF1TB 1 Yes
FO-644PLF2TB 2 Yes
FO-644PLF5TB 5 Yes
FO-644PLF10TB 10 Yes
FO-644PLF25TB 25 Yes
6? x 56? x 3 ? ID FO-656PLF1M 1 Yes
6? x 56? Threaded Base FO-656PLF1/ 2TB 0.5 Yes
FO-656PLF1TB 1 Yes
FO-656PLF2TB 2 Yes
FO-656PLF5TB 5 Yes
FO-656PLF25TB 25 Yes
6 ? x 18? x 29/ 16? ID FO-718PLP3 0.3 No
FO-718PL1/ 2 0.5 No
FO-718PL01 1 Yes
FO-718PL02 2 Yes
FO-718PL05 5 Yes
FO-718PL10 10 Yes
FO-718PL15 15 Yes
FO-718PL25 25 Yes
FO-718PL50 50 Yes
6 ? x 36? x 29/ 16? ID FO-736PLP3 0.3 No
FO-736PL1/ 2 0.5 No
FO-736PL05 5 Yes
FO-736PL15 15 Yes
8? x 221/ 8? x 2? ID FO-822PLP3 0.3 No
FO-822PL1/ 2 0.5 No
FO-822PL05 5 No
8? x 29 ? x 2? ID FO-829PL05 5 No
Dual Media Cartridge Information
Dimensions Model Number Nominal Micron Efficiency
Upstream Downstream
6? OD x 29? OAL x 3-1/ 2? ID FO-629PLF5/ 1M 5 1
FO-629PLF15/ 2M 15 2
FO-629PLF25/ 5M 25 5
6? OD x 44? OAL x 3-1/ 2? ID FO-644PLF5/ 1M 5 1
FO-644PLF15/ 2M 15 2
FO-644PLF25/ 5M 25 5
6? OD x 56? OAL x 3-1/ 2? ID FO-656PLF5/ 1M 5 1
FO-656PLF15/ 2M 15 2
FO-656PLF25/ 5M 25 5
AC SERIES - AQUACON WATER ABSORBING CARTRIDGES
Removes free and emulsified water to less than 2 ppm
Differential pressure increase alerts operator to change cartridges
Effectively filters silt and other particulates
No media migration or ? linting?
Easy to install and remove
Does not affect oil additives
Fits standard filter housings
Aquacon Cartridges have a patented* construction for removing dirt and water from hydrocarbon and other oils as well as gases. The outer media layer filters out silt, rust and other particulate contaminants. The inner layers absorb water and chemically bond it so that no water will release downstream.
When the Aquacon Cartridge reaches its water holding limit, the media swells shut and the differential pressure rapidly increases. This signals the operator that the cartridge must be changed.
APPLICATIONS
Gasoline
Kerosene
Diesel Fuel
Insulating Oil
Biodiesel
Hydraulic Oil
Turbine Lube Oil
Quench Oil
Synthetic Oil
Phosphate Ester Oil
TECHNICAL INFORMATION
Maximum operating temperature is 250 F.
Aquacon Cartridges will shut off flow when loaded with water or dirt. Appropriate precautions should be taken in critical applications where oil flow must be maintained.
With some lube and hydraulic oils all of the water may not be removed in one pass, and extra passes will be required for total removal.
Water capacity for the AC-718 cartridges ranges from 2 to 4 quarts.
WARNING: Absorbent-type monitor cartridges will not remove water from fuel containing alcohol-blending agents ( commonly called gasohol) . For removal of solids, please use Velcon particle removal filters specifically made for gasohol. Consult your Velcon representative.
CARTRIDGE INFORMATION
New types of Aquacon Cartridges are being introduced continually.
Contact your local Velcon Representative for up to-date information.
Model
Number
Micrometer Reading
I.D.
Inches
O.D.
Inches
Length
Inches
Collapse
Pressure, psi
Interchange
Information
Normal
Betax= 75
AC-21005( 1)
5
40
1
2.625
9.75
75
Fits Velcon VF-31 Housings
AC-5121/ 2E( 2)
0.5
3
1.875
5.625
12.125
75
Fits Velcon VF-61 Housings
AC-51205
5
40
1.875
5.625
12.125
75
AC-61405
5
40
3.5
6
14 .5
100
Interchanges with Velcon
FO-614PLF, FO-629PLF, and FO-644PLF Series Cartridges
AC-62905
5
40
3.5
6
29.5
100
AC-64405
5
40
3.5
6
44
100
AC-718P3( 2)
0.3
2
2.5625
6.25
18
75
Fits Velcon industrial housings and portable filters, interchangeable with Velcon FO-718PL and FO-736PL Series Cartridges
AC-718P4D
0.4
2.5
2.5625
6.25
18
75
AC-7181/ 2( 2)
0.5
3
2. 5625
6.25
18
75
AC-71801
1
6
2.5625
6.25
18
75
AC-71805
5
40
2.562 5
6.25
18
75
AC-7361/ 2( 2)
0.5
3
2.5625
6.25
36
75
AC-73601
1
6
2.5 625
6.25
36
75
AC-73605
5
40
2.5625
6.25
36
75
Notes:
( 1) The AC-21005 will fit into many existing housings that take ? string-wound? cartridges.
Check to confirm that the 9 3/ 4? length will seat properly in the housing.
( 2) The AC-5121/ 2E, AC-718P3, AC-7181/ 2 and AC-7361/ 2 are increased surface area/ reduced water capacity cartridges specifically designed for circuit breaker oil.
FG SERIES - FIBREGLASS CARTRIDGES
Velcon Fiberglass Depth Cartridges have proven superior in filtering colloidal or slimy contaminants. Lube oil and EDM coolant filtration are this type of application where fiberglass elements consistently filter better with dramatically longer life than other types of media.
APPLICATIONS
Hydraulic Oils
Cutting Oils
Glycols
Degreasing Fluids
Water Emulsion Coolants
Naphtha
Lube Oils
Ethyl Alcohol
Boiler Feed Water
Fuels
Synthetic Oils
Biodiesel
SPECIFICATIONS
100 psi collapse strength
5 - 9 operating pH range
98% + filtration efficiency
250 F maximum operating temperature
Recommended changeout : 25 psid
> High Efficiency, Long Life Cartridges for Oils and Fuels
CARTRIDGE INFORMATION
FG SERIES
Velcon Model Number
O.D.
( Inches)
I.D.
( Inches)
Length
( Inches)
Micron Rating
FO-614FG10
6
3.5
14.5
10
FO-614FG10P*
6
3.5
14.5
10
FO-614FG25
6
3.5
14.5
25
FO-618FG10P*
6
3.5
18
10
FO-622FG25
6
3.5
22
25
FO-62 9FG2
6
3.5
29.5
2
FO-629FG2P*
6
3.5
29.5
2
FO-629FG10
6
3.5
29.5
10
FO-629FG10P*
6
3.5
29.5
10
FO-629FG25
6
3.5
29.5
25
FO-636FG5
6
3.5
35.875
5
FO-636FG10
6
3.5
35.875
10
FO-644FG2
6
3.5
44
2
FO-644FG5
6
3.5
44
5
FO-644FG25
6
3.5
44
25
FO-644FG40P*
6
3.5
44
40
* P designates individual unit cartons
FGA SERIES
FO-618FGA5
6
2.5625
18
5
FO-618FGA10
6
2.5625
18
10
FO-618FGA25
6
2.5625
18
25
FO-629FGA5
6
2.5625
29.5
5
FO-629FGA10
6
2.5625
29.5
10
FO-636FGA5
6
2.5625
35.875
5
FO-636FGA10
6
2.5625
35.875
10
The primary difference between FG and FGA Series is the inner diameter
Tampilkan Lebih Banyak